Leave Your Message
DR-XGN-24 KV Ring Main Unit
High Voltage Switchgear Series

DR-XGN-24 KV Ring Main Unit

DR-XGN-24 box type AC metal closed ring switch equipment,is a new generation of sulfur hexafluoride load switch,can be configured circuit breaker,isolation switch,current transformer,voltage transformer,arrester and other electrical components.The whole cabinet adopts air insulation,suitable for  distribution  automation,both  compact  and  expandable   metal closed switchgear,with beautiful appearance,simple structure,small size,flexible operation, reliable interlock and other characteristics.

The ring network cabinet is suitable for the ring network power supply system with rated voltage of 24ky, and is widely used in industrial and civil cable ring network and power supply terminal projects, Especially suitable for the following places: power distribution in urban residential areas, small secondary substations, opening and closing offices,industrial and mining enterprises, shopping malls, airports, subways. tunnels, wind power generation. etc.

    Model meaning

    20241106-德锐电气(2024版)(中英文)最终定稿版-60.jpg

    Normal service condition

    ◆Altitude                                                                     ≤1000m

    ◆Maximum ambient temperature                       +40℃

    ◆Minimum ambient temperature                        -35℃

    ◆Maximum daily temperature difference          25K

    ◆Daily average relative humidity                         ≤95%

    ◆Monthly average relative humidity                   ≤90%

    ◆Earthquake resistance                                          level 8

    ◆System rated frequency                                       50Hz

    ◆SF6leakage rate                                                     ≤0.1%                  

    ◆Enclosure protection class                                  IP3X

    Main feature

    ◆Increase the main transformer capacity and improve the power supply capacity of the substation.

    ◆Improve the power transmission capacity of distribution lines and reduce the number of distribution lines.

    ◆Increase the power supply radius of the medium voltage line.

    This voltage level earlier in a small area trial operation,by the requirements of the State grid company,by Jiangsu provincial pilot promotion of 20kV voltage level,now the southern network is also ready to start promoting 20kV voltage level in Guangdong and other places,it can be predicted that the final 24kV equipment will dominate the market.

    Main technical parameters

    Item

    Unit

    20kV SF Ring switchgear

    Rated voltage

    kV

    24

    Rated frequency

    Hz

    50

    Rated current

    A

    630A≤100(Load switch-fuse combination cabinet)

    Rated short-circuit breaking current

    kA

    31.5

    Rated closing current(peak)

    kA

    50

    Rated heat stable current

    kA/3S

    20

    Rated dynamic stable current(peak)

    kA

    50

    Insulation level

    Power frequency withstand voltage

    Phase to phase and ground to ground

    kV/1min

    65

    Fracture

    kV/1min

    79

    Lightning impulse withstand voltage

    Phase to phase and ground to ground

    kV

    125

    Fracture

    kV

    145

    Rated active load breaking current

    A

    630

    Rated cable charging breaking current

    A

    25

    Main loop resistance

    μΩ

    ≤300

    Kinetic function

     

    Spring type:DC/AC 220V/48V

    Rated transfer current

    A

    1400

    Mechanica life

     

    Load switch:3000;Ground switch:2000

    Primary scheme

    Primary plan number

    DC01

    Primary plan number

    DC08

    Main bus TMY-3(40×8)

     图片11.jpg

    Main bus TMY-3(40×8)

     图片12.jpg

    DR-XGN□-24 Primary system diagram

    DR-XGN□-24 Primary system diagram

    Disposition

    Incoming cabinet

    Disposition

    Outlet cabinet

    Load switch FLN□-24D

    1

    Load switch FLN□-24D

     

    Load switch FLRN□-24D

     

    Load switch FLRN□-24D

    1

    Live display DXN-T/Q

    1

    Live display DXN-T/Q

    1

    The current transformer

     

    The current transformer

     

    Fuse XRNP-24/□A

     

     Fuse XRNP-24/□A

     

    Voltage transformer JDZ-24

     

    Voltage transformer JDZ-24

    3

    Lightning arrester HY5WS-33/85

    3

    Lightning arrester HY5WS-33/85

     

     Fuse XRNT-24/□A

     

     Fuse XRNT-24/□A

    3

    Measuring instrument

     

    Measuring instrument

     

    Protection mode

     

    Protection mode

     

    Auxiliary function

     

    Auxiliary function

     

    Mode of operation

    Manual operation

    Mode of operation

    Manual operation

    Cabinet width x Depth x height(mm)

    650×1200×2000

    Cabinet width x Depth x height(mm)

    650×1200×2000

    Primary plan number

    DC01

    Primary plan number

    DC08

    Main bus TMY-3(40×8)

     图片13.jpg

    Main bus TMY-3(40×8)

     图片14.jpg

    DR-XGN□-24 Primary system diagram

    DR-XGN□-24 Primary system diagram

    Disposition

    Incoming cabinet

    Disposition

    Outlet cabinet

    Load switch FLN□-24D

    1

    Load switch FLN□-24D

     

    Load switch FLRN□-24D

     

    Load switch FLRN□-24D

    1

    Live display DXN-T/Q

    1

    Live display DXN-T/Q

    1

    The current transformer

     

    The current transformer

     

    Fuse XRNP-24/□A

     

     Fuse XRNP-24/□A

     

    Voltage transformer JDZ-24

     

    Voltage transformer JDZ-24

    3

    Lightning arrester HY5WS-33/85

    3

    Lightning arrester HY5WS-33/85

     

     Fuse XRNT-24/□A

     

     Fuse XRNT-24/□A

    3

    Measuring instrument

     

    Measuring instrument

     

    Protection mode

     

    Protection mode

     

    Auxiliary function

     

    Auxiliary function

     

    Mode of operation

    Manual operation

    Mode of operation

    Manual operation

    Cabinet width x Depth x height(mm)

    650×1200×2000

    Cabinet width x Depth x height(mm)

    650×1200×2000

    Overall dimension

    20241106-德锐电气(2024版)(中英文)最终定稿版-62.jpg

    ring main unit