Leave Your Message
China Suppliers of MNS Low Voltage Withdrawable Switchgear for Factory Power Distribution and Control
Hot Products

China Suppliers of MNS Low Voltage Withdrawable Switchgear for Factory Power Distribution and Control

This series of low-voltage withdrawable switchgear is expertly designed for diverse applications, including power plants, substations, petrochemical industries, metallurgical steel rolling, transportation energy, light industry, textile production, and other manufacturing and mining enterprises. It is ideal for residential areas and high-rise buildings as well. The switchgear facilitates efficient power conversion, distribution, and control for power systems operating at a frequency of AC 50-60Hz and a rated working voltage of AC 660V and below. As one of the leading China suppliers, our factory guarantees high-quality and reliable switchgear solutions tailored to meet the needs of various sectors

    Conditions of use

    • The ambient air temperature shall not be higher than +40℃ and not lower than -5℃, and its average temperature within 24 hours shall not be higher than +35℃;
    • Relative humidity: in clean air, it doesn’t exceed 50% at a maximum temperature of +40°C; higher relative humidity is allowable at lower temperatures (e.g. 90% at +20°C); however, it should be considered that occasional condensation may occur due to temperature change.
    • Altitude shall not exceed 2000m;
    • This equipment is suitable for transportation and storage at temperatures ranging from -25℃ to +55℃, and it can reach +70℃ in a short period of time (not exceeding 24 hours). At these extreme temperatures, the equipment should not suffer any irreparable damage and should be able to function normally under normal conditions;

    Note: When the above normal service conditions cannot meet the usage requirement, it shall be negotiated between the user and the manufacturer.

    When this equipment is used on offshore oil drilling platforms and nuclear power plants, a separate technical agreement should be signed.

    Technical parameter

    Rated insulation voltage AC690V
    Rated working voltage AC400V
    Rated current of main busbar ≤6300A
    Rated withstand current of main busbar(1s) 50kA, 80kA
    Rated peak withstand current of main busbar 105kA, 176kA
    Maximum working current of distribution busbar (vertical busbar) 1000A
    Distribution busbar (peak current of vertical busbar)
    Standard type 105kA(maximum)/0.1s
    Enhanced type 176kA(maximum)/0.1s

    Protection level

    Compliant with IEC529 and DIN40050 standards

    • IP30 provides protection for solid larger than φ2.5MM
    • IP40 provides protection for solid larger than φ1.0MM
    • IP54 provides protection against dust and splash in any direction

    When ordering IP54 protection level, it should be negotiated with the manufacturer.

    Cabinet structure

    The basic structure of the switchgear cabinet is assembled by C-shaped profiles. C-shaped profiles are made by bending steel plates with E=25mm as the modular installation hole.

    All cabinet frames and inner partitions are treated with galvanized purification. The surrounding door panels and side panels are coated with high-voltage electrostatic spraying.

    The basic structure of the cabinet is shown in Figure 1: the basic dimensions of the cabinet are shown in Figure 2, Tables 1 and 2.

    Switch cabinet type

    Power distribution center cabinet (PC) Emax, MT, 3WN, AH, ME series circuit breakers can be used.
    Motor control center cabinet (MCC) Assembled from draw-out units of various sizes, the main switch of each circuit adopt high breaking molded case circuit breaker or rotary load switch with fuse, Power factor automatic compensation cabinet (with manual, automatic and remote power factor compensation device).
    Cabinet frame structure composed of c-shaped profiles (Figure 1)
    Figure 1: Cabinet frame structure composed of C-shaped profiles
    Cabinet schematic diagram (Figure 2)
    Figure 2: Cabinet schematic diagram

    Installation diagram

    Solution 1: Welding installation

    Solution 2: Bolt installation

    Installation diagram
    Installation diagram (Welding & Bolt solutions)

    Installation diagram of busbar bridge

    Installation diagram of busbar bridge
    Installation diagram of busbar bridge
    Frequently Asked Questions
    What are the ambient temperature requirements for using this equipment?
    The ambient air temperature must not exceed +40℃ and should not be lower than -5℃. The average temperature within a 24-hour period must not exceed +35℃.
    What is the maximum installation altitude for this equipment?
    The installation altitude of the equipment must not exceed 2000 meters.
    What are the rated insulation and working voltages?
    The rated insulation voltage is AC690V, and the rated working voltage is AC400V.
    What IP protection levels does this switchgear offer?
    It complies with IEC529 and DIN40050 standards, offering IP30 (protection for solids > 2.5mm), IP40 (protection for solids > 1.0mm), and IP54 (protection against dust and splash, which requires negotiation with the manufacturer when ordering).
    What are the options for cabinet installation?
    There are two installation solutions available: Solution 1 is Welding installation, and Solution 2 is Bolt installation.