China Factory DFW-12(35kV) High Voltage Cable Branch Box European Style – Durable, Insulated, Suppliers Ready
■Model meaning
■Environmental conditions of use
- The altitude shall not exceed 1000 meters.
- Operating ambient temperature: -30°C ~ 40°C.
- Relative humidity ≤ 95%.
- The ambient air should not be significantly polluted by flammable gas, but can be polluted by smoke dust and corrosive gas, and the pollution level should not exceed class III in GB/T5582.
- No frequent severe vibration.
■Main technical parameter
| Item name | Unit | Argument | Remark |
|---|---|---|---|
| Rated voltage | kV | 12 | It can be equipped with load switch, circuit breaker, fuse, etc., and the technical parameters are shown in the instructions of the accessory |
| Rated frequency | Hz | 50 | |
| Rated current | A | 630 | |
| 1min power frequency withstand voltage | kV | 42 | |
| Lightning impulse withstand voltage | kV | 75 | |
| Protection level | IP54 | ||
| Outline dimension (L×W×H) | mm | 650×1150×880 ~ 1300×1500×1200 | |
■European type cable branch box structure diagram
If the cable branch box cannot be placed due to site limitation, it can be directly combined with cable joint to form multiple cable branches (without the need for busbar, the connection method is shown in the following example) and placed in the cable trench or its location.
Example 1: Four-way incoming and outgoing lines
Each phase consists of two European type front joints and two European type rear joints, with one European type connected to butt sleeve in the middle. The end of the European type rear joint is sealed with insulator and semiconductive end cap. The example is shown in the following figure:
Example 2: 2 incoming 3 outgoing
Each phase consists of three European type front joints and two European type rear joints, connected by European type butt sleeve in the middle. The end of the European type rear joint is sealed with insulator and semiconductive end cap. The example is shown in the following figure:
Note: Cable branches can be expanded or reduced as needed, and can be enclosed in a box or buried directly in cable trench.
■European type cable branch box structure diagram
■European type cable branch (connection) box structure diagram
Note: Cable branches can be expanded or reduced as needed, and can be enclosed in a box or buried directly in cable trench.
■Ordering information (box configuration solution)
| Specification and model | Wiring solution | Internal arrangement | Outline dimension |
|---|---|---|---|
| DFW10-2 | ![]() |
![]() |
580×550×950 |
| DFW10-3 | ![]() |
![]() |
700×550×950 |
| DFW10-4 | ![]() |
![]() |
820×550×950 |
| DFW10-5 | ![]() |
![]() |
940×550×950 |
| DFW10-6 | ![]() |
![]() |
1060×550×950 |
| DFW10-7 | ![]() |
![]() |
1180×550×950 |
| DFW10-8 | ![]() |
![]() |
820×650×1000 |
| DFW10-9 | ![]() |
![]() |
940×650×1000 |
■Cable plug installation diagram
■European type cable branch box foundation diagram
?Frequently Asked Questions (FAQ)
A: The European type cable branch box has a rated voltage of 12kV and meets the IP54 protection level standard, ensuring reliable outdoor performance.
A: The equipment is designed to operate safely within an ambient temperature range of -30°C to 40°C.
A: Yes, the cable branches can be expanded or reduced according to project requirements. They can be enclosed in a box or placed directly in a cable trench.
A: The box can be equipped with various accessories including load switches, circuit breakers, and fuses depending on the specific model requirements.
A: You can refer to the ordering information table to select the model (DFW10-2 to DFW10-9) based on the required wiring solution, internal arrangement, and outline dimensions.