China Pad-Mounted Transformer - Custom Box-Type Substation Suppliers | Derui Factory Quality Solutions
Model meaning
Conditions of use
Product characteristics
List of fuse configuration for high voltage protection
| Rated capacity of transformer (kVA) | Low voltage side (0.4kV) rated current (A) | High voltage side (10kV) rated current (A) | Plug-in fuse capacity (A) | Backup fuse capacity (A) | Low voltage equipped main switch capacity (A) |
|---|---|---|---|---|---|
| 50 | 72.2 | 2.89 | 4 or 6 | 10 | 100 |
| 80 | 115.5 | 4.62 | 10 | 20 | 160 |
| 100 | 144.3 | 5.77 | 10 | 20 | 200 |
| 125 | 180.4 | 7.22 | 10 | 25 | 250 |
| 160 | 230.9 | 9.24 | 15 | 40 | 315 |
| 200 | 288.7 | 11.55 | 20 | 40 | 400 |
| 250 | 360.8 | 14.43 | 25 | 50 | 500 |
| 315 | 454.7 | 48.19 | 31.5 | 80 | 630 |
| 400 | 577.4 | 23.09 | 40 | 80 | 800 |
| 500 | 721.7 | 28.87 | 50 | 100 | 1000 |
| 630 | 909.3 | 36.37 | 65 | 125 | 1250 |
| 800 | 1154.7 | 46.19 | 80 | 125 | 1600 |
| 1000 | 14434 | 57.75 | 100 | 200 | 2000 |
| 1250 | 1804.2 | 72.17 | 125 | 250 | 2500 |
| 1600 | 2309.4 | 92.38 | 160 | 320 | 3200 |
Main technical parameter table
Technical parameter of 6kV and 10kV S□ series oil immersed distribution transformer
| Rated capacity (kVA) | Voltage combination (kV) | Connection group symbol | Loss (kW) | Off-load current (%) | Short circuit impedance (%) | Weight (kg) | Outline dimension mm L×W×H | Track gauge, longitudinal/transverse | ||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| HV | LV | Off-load | Load 75% | Body weight | Oil weight | Total weight | ||||||
| 30 | 10.5 10 6.3 | 0.4 | Dyn11 Yzn11 Yyn0 | 0.08 | 0.63/0.6 | 1.5 | 4 | 185 | 70 | 310 | 790×660×925 | 550/400 |
| 50 | 0.1 | 0.91/0.87 | 1.3 | 255 | 85 | 395 | 820×675×1030 | 550/400 | ||||
| 63 | 0.11 | 1.09/1.04 | 1.2 | 280 | 95 | 430 | 845×690×1065 | 550/400 | ||||
| 80 | 0.13 | 1.31/1.25 | 1.2 | 320 | 100 | 480 | 865×715×1075 | 550/550 | ||||
| 100 | 0.15 | 1.58/1.5 | 1.1 | 380 | 110 | 540 | 880×720×1120 | 550/550 | ||||
| 125 | 0.17 | 1.89/1.8 | 1.1 | 444 | 115 | 600 | 910×750×1110 | 550/550 | ||||
| 160 | 0.2 | 2.31/2.2 | 1 | 510 | 130 | 690 | 910×750×1200 | 550/550 | ||||
| 200 | 0.24 | 2.73/2.6 | 1 | 640 | 150 | 840 | 1220×745×1220 | 550/550 | ||||
| 250 | 0.29 | 3.2/3.05 | 0.9 | 720 | 190 | 950 | 1240×775×1345 | 660/660 | ||||
| 315 | 0.34 | 3.83/3.65 | 0.9 | 835 | 200 | 1065 | 1230×750×1345 | 660/660 | ||||
| 400 | 0.41 | 4.52/4.3 | 0.8 | 1010 | 240 | 1255 | 1330×825×1375 | 660/660 | ||||
| 500 | 0.48 | 5.41/5.15 | 0.8 | 1170 | 260 | 1485 | 1455×915×1390 | 660/660 | ||||
| 630 | Dyn11 Yyn0 | 0.57 | 6.2 | 0.6 | 4.5 | 1375 | 320 | 1800 | 1540×920×1510 | 660/660 | ||
| 800 | 0.7 | 7.5 | 0.6 | 1620 | 365 | 2120 | 1650×1035×1555 | 820/820 | ||||
| 1000 | 0.83 | 10.3 | 0.6 | 1780 | 405 | 2450 | 1855×1235×1600 | 820/820 | ||||
| 1250 | 0.97 | 12 | 0.5 | 2065 | 560 | 2855 | 1925×1285×1680 | 820/820 | ||||
| 1600 | 1.17 | 14.5 | 0.5 | 2470 | 650 | 3400 | 2025×1355×1730 | 820/820 | ||||
| 2000 | 1.55 | 18.3 | 0.4 | 5 | 2700 | 695 | 4460 | 2190×1900×1950 | 820/820 | |||
| 2500 | 1.83 | 21.2 | 0.4 | 3230 | 870 | 5330 | 2240×1940×1980 | 1070/1070 | ||||
Note:
1. The load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 connection group, and the load loss values below the diagonal line are applicable to the Yn0 connection group.
2. The outline dimensions are for reference only during selection, and the final dimensions are subject to the product's outline drawing.
Basic structure
The box substation should be installed on a horizontal concrete platform, which should be able to withstand the weight. Due to the fact that most of the weight of the box substation is concentrated at the rear of the box containing the transformer body, the front cabinet is mostly empty and relatively light in weight. Therefore, the rear of the platform should be sturdy and able to withstand the weight of the combined transformer. Meanwhile, it is also required that the front and rear countertops be flat (generally, it is not easy to achieve flatness, so the foundation of the front cabinet can be slightly lower than that of the rear transformer body, and after being in place, it can be sealed with concrete) to ensure smooth installation of the box substation.

- 1 Regarding the combination size of dimensions;
- 2 The concrete foundation should have a smooth surface. After the installation of the combined substation, the surrounding area of the base should be sealed with cement;
- 3 The shape of ground bars and cable fixing brackets can be determined according to the actual situation;
- 4 Cable fixing brackets and ground bars should be pre-embedded;
- 5 The position of the cable holes for incoming and outgoing lines depends on the specific situation;
- 6 After the installation of the combination substation, there must be a gap of no less than 1.5m on the front of the switch to facilitate operation;
- 7 The grounding grid can be made of 12 plated round steel or 30 x 4 galvanized flat steel, and the ground wire resistance should meet the requirements of the power department.
Note: The dimensions of L, W and H are determined according to the actual engineering configuration.