Introducing the KYN61-40.5 armored removable AC metal enclosed switchgear, a highly efficient solution for three-phase AC 50Hz 40.5kV power systems. This switchgear is specially designed for distribution rooms in power plants, substations, and industrial and mining enterprises, ensuring reliable reception and distribution of electric energy. With essential functions such as circuit control, protection, and monitoring, this switchgear is ideal for both general power systems and applications with frequent operational demands, Manufactured with an assembled structure, this product enhances both aesthetic appeal and manufacturing precision. The busbar is equipped with advanced insulation techniques, including heat-shrinkable insulation materials or epoxy coatings, to optimize electrode shape and functionality. The compact cabinet structure incorporates complete five prevention features, ensuring safety and reliability, This switchgear adheres to stringent standards such as GB3096, GB/T11022, IEC60298, and DT/L404, making it a trusted choice among China suppliers and factories. Choose the KYN61-40.5 switchgear for superior performance and durability in your electrical distribution needs

    Model meaning

    Model meaning diagram of Derui Electric switchgear

    Conditions of use

    • Altitude: ≤1000m;
    • Ambient temperature: upper limit of ambient air temperature +40℃, lower limit -15℃;
    • Relative humidity: The daily average relative humidity shall not exceed 95%; monthly average relative humidity shall not exceed 90%;
    • Seismic intensity: The seismic intensity does not exceed 8 degrees
    • It's not suitable for places with obvious pollution such as corrosive or flammable gas and water vapor, etc.
    • When the above normal service conditions are not met, the user can negotiate with the manufacturer.

    Product characteristics

    • The switchgear is designed with complete metal armor and fully enclosed structure.
    • The interior of the switchgear is divided into four independent compartments: circuit breaker room, busbar room, cable room and relay instrument room. Each functional unit is sealed with metal plates and equipped with independent pressure release channel and release door.
    • The switch cabinet body is made of high-quality cold-rolled steel plate processed by CNC sheet metal forming, and connected by high-strength bolts, nuts and rivet nuts. The surface of the components is sprayed or galvanized; it can be equipped with ZN85A vacuum circuit breaker and French Schneider's SF1, SF2 type and Alstom FP series SF6 circuit breaker to meet the needs of different users.
    • The switchgear can perform circuit breaker opening and closing, moving-in/out, and ground switch opening and closing with the cabinet door closed.
    • The switchgear is designed to prevent misoperation of circuit breaker, prevent pushing trolley with load, prevent ground switch from transmitting power at the grounding position, and prevent accidental entry into live compartments, meeting the "five prevention" functions.
    • The convenient door panel observation window of the switchgear allows for viewing of the circuit breaker's on/off status, trolley position, energy storage position, and ground switch's on/off status.
    • The switchgear trolley has good interchangeability, and the secondary wires are located in spacious cable tray, which are beautiful and easy to find. The primary cable connection is convenient.
    • The protection level of the outer shell is IP4X, while the protection level is IP2X between small rooms and when the circuit breaker door is open. The installation and maintenance of the cabinet can be carried out on the front or back. The switchgear can not only be installed in a face-to-face or back-to-back double row arrangement, but also can be installed against the wall according to specific project requirements, which saves floor space and improves the safety and flexibility of the switchgear.

    Outline dimension and schematic diagram of switchgear structure

    Schematic diagram of switchgear structure 1Schematic diagram of switchgear structure 2
    1. Shell
    2. Valve bracket
    3. Circuit breaker trolley
    4. Contact box
    5. Busbar sleeve
    6. Instrument room
    7. Pressure relief device
    8. Current transformer
    9. Ground switch

    Technical parameter

    Item Unit Argument
    Rated voltage kV 40.5
    Rated frequency Hz 50
    Rated current of main busbar A 630,125,016,002,000
    Rated current of branch busbar A 63,012,501,600
        Phase-phase, phase-ground Isolating distance
    Rated insulation level 1min power frequency withstand voltage (effective value) kV 95 115
    Lightning impulse withstand voltage (peak value) kV 185 215
    1min power frequency withstand voltage of auxiliary control circuit V 2000
    Rated short-circuit breaking current kA 25, 31.5
    Rated short-circuit making current (peak value) kA 63, 80
    Rated short-time withstand current (4S) kA 25, 31.5
    Rated peak withstand current kA 63, 80
    Rated voltage of auxiliary control circuit V AC or DC110V/220V
    Protection level   IP4X / IP2X
    Outline dimension (Width × Depth × Height) mm 1400x2800(3000)x2800 (*number in parentheses represents SF6 trolley solution)
    Weight kg 2300 About 2300

    Frequently Asked Questions (FAQ)

    Q1: What are the installation altitude limit and ambient temperature requirements for this switchgear?
    The standard service conditions require an altitude of ≤1000m. The ambient air temperature should have an upper limit of +40℃ and a lower limit of -15℃.
    Q2: Which types of circuit breakers can be configured inside the switch cabinet?
    The switch cabinet can be flexibly equipped with ZN85A vacuum circuit breakers, French Schneider's SF1 or SF2 types, and Alstom FP series SF6 circuit breakers to meet different project needs.
    Q3: How does the switchgear ensure safety during operations?
    It features a robust "five prevention" interlock design that prevents misoperation of the circuit breaker, pushing the trolley with load, ground switch power transmission at the grounding position, and accidental entry into live compartments. All standard operations can be performed with the cabinet door closed.
    Q4: What is the enclosure and internal compartment protection level?
    The outer shell of the switchgear offers an IP4X protection rating, while the protection level between internal compartments and when the circuit breaker door is open is IP2X.
    Q5: Can the switchgear structure layout be customized to save floor space?
    Yes. The cabinet can be installed against the wall, face-to-face, or in a back-to-back double row arrangement according to specific layout requirements, saving floor space while maintaining high safety and flexibility.