The KYN28-24 indoor AC metal armored removable switchgear, hereafter referred to as the switchgear, is designed for three-phase power systems operating at a frequency of 50Hz and a rated voltage of 24kV. This advanced switchgear is ideally suited for use in power plants, substations, industrial and mining enterprises, as well as high-rise buildings, to effectively receive, distribute, control, protect, and monitor electrical energy.

Manufactured by leading China suppliers and factories, this switchgear incorporates a variety of safety features to prevent misoperation. These include safeguards against trolley movement while under load, mechanisms to prevent the ground switch from closing a circuit breaker that is in the closed position, protections against the live ground switch from closing, and barriers to accidental entry into live compartments.

The secondary circuit of the switchgear is equipped with state-of-the-art control and protection components, and the bus utilizes heat shrinkable insulation materials or epoxy coating insulation to enhance the electrode shape. With its compact structure, this power distribution equipment showcases advanced technology, stable performance, a rational design, ease of use, and exceptional safety and reliability, making it a preferred choice among electrical solutions in China and beyond.

    Model meaning

    Model meaning description

    Product standard

    • GB311.1 Insulation co-ordination-Part1:Definitions,principles and rules
    • GB1984 High-voltage alternatiing-current circuit-breakers
    • GB3906 Alternating-current metal-enclosed switchgear and controlgear for rated voltages above 3.6kVand up to and including 40.5kV
    • GB/T11022 Common specifications for high-voltage alternating-current switchgear and controlgear standards
    • Common specifications for high-voltageswitchgear and controlgear standards
    • IEC62271-20:2003 High-voltage switchgear and controlgear-Part 200:AC metal-enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 52kV

    Conditions of use

    • Altitude: ≤1000m;
    • Ambient temperature: upper limit of ambient air temperature +40℃, lower limit -15℃;
    • Relative humidity: The daily average relative humidity shall not exceed 95%; monthly average relative humidity shall not exceed 90%;
    • Seismic intensity: The seismic intensity does not exceed 8 degrees;
    • It's not suitable for places with obvious pollution such as corrosive or flammable gas and water vapor, etc.
    • When the above normal service conditions are not met, the user can negotiate with the manufacturer.

    Product characteristics

    • The switchgear is designed with complete metal armor and fully enclosed structure.
    • The interior of the switchgear is divided into four independent compartments: circuit breaker room, busbar room, cable room and relay instrument room. Each functional unit is sealed with metal plates and equipped with independent pressure release channel and release door.
    • The switch cabinet body is made of high-quality cold-rolled steel plate processed by CNC sheet metal forming, and connected by high-strength bolts, nuts and rivet nuts. The surface of the components is sprayed or galvanized; it can be equipped with VS1(ZN63A) vacuum circuit breaker and ABB's VD4 and Schneider's HVX series circuit breakers to meet the needs of different users.
    • The switchgear can perform circuit breaker opening and closing, moving-in/out, and ground switch opening and closing with the cabinet door closed.
    • The switchgear is designed to prevent misoperation of circuit breaker, prevent pushing trolley with load, prevent ground switch from transmitting power at the grounding position, and prevent accidental entry into live compartments, meeting the "five prevention" functions.
    • The convenient door panel observation window of the switchgear allows for viewing of the circuit breaker's on/off status, trolley position, energy storage position, and ground switch's on/off status.
    • The switchgear trolley has good interchangeability, and the secondary wires are located in spacious cable tray, which are beautiful and easy to find. The primary cable connection is convenient.
    • The protection level of the outer shell is IP4X, while the protection level is IP2X between small rooms and when the circuit breaker door is open. The installation and maintenance of the cabinet can be carried out on the front or back. The switchgear can not only be installed in a face-to-face or back-to-back double row arrangement, but also can be installed against the wall according to specific project requirements, which saves floor space and improves the safety and flexibility of the switchgear.

    Schematic diagram of switchgear structure

    KYN28 switchgear structure part 1
    KYN28 switchgear structure part 2

    Technical parameter

    Item Unit Argument
    Rated voltage kV 24
    Rated frequency Hz 50/60
    Rated insulation level 1min power frequency withstand voltage (effective value) kV Phase-phase, phase-ground 65 Isolating distance 79
    Lightning impulse withstand voltage (peak value) kV 125 145
    Power frequency withstand voltage of auxiliary control circuit V 2000
    Rated current A 63,012,501,600,200,000,000,000
    Rated short-circuit breaking current KA 20 25 31.5
    Rated short-circuit making current (peak) KA 50 63 80
    Rated short-time withstand current (4s) KA 20 25 31.5
    Rated peak withstand current KA 50 63 80
    Rated voltage of auxiliary control circuit V 110V/220V DC or AC 110V/220V
    Protection level   IP4X / IP2X
    Outline dimension (Width×Depth×Height) mm 800×1810×2430 / 1000×1810×2430
    Weight kg 840~1440

    Frequently Asked Questions (FAQ)

    Q Which international and national standards does this switchgear comply with?

    This switchgear complies with major industry standards, including GB311.1 (Insulation co-ordination), GB1984 (High-voltage AC circuit-breakers), GB3906, GB/T11022, and IEC62271-200 for AC metal-enclosed switchgear.

    Q What are the environmental limits and conditions of use for this system?

    It is designed for altitudes up to 1000m, ambient temperatures between -15℃ and +40℃, and a daily average relative humidity not exceeding 95% (monthly average ≤90%). It is not suitable for environments with corrosive, flammable gases, or heavy water vapor.

    Q How is the switchgear structured internally for safety?

    The unit features a fully enclosed metal-armored structure divided into four independent compartments: circuit breaker room, busbar room, cable room, and relay instrument room. Each compartment is sealed with metal plates and has its own pressure release channel.

    Q Which vacuum circuit breaker models can be installed in this cabinet?

    It is highly compatible and can be equipped with VS1 (ZN63A) vacuum circuit breakers, as well as premium options like ABB's VD4 and Schneider's HVX series circuit breakers.

    Q What protection ratings and installation options are supported?

    The outer shell has an IP4X protection rating (IP2X between compartments and when the door is open). It supports flexible installation against walls, back-to-back, or in double-row arrangements, saving floor space and simplifying front/back maintenance.