Leave Your Message
China XGN-12 12KV Ring Main Unit - Quality Metal Enclosed RMU from Trusted Suppliers & Factory
Hot Products

China XGN-12 12KV Ring Main Unit - Quality Metal Enclosed RMU from Trusted Suppliers & Factory

The XGN□-12 modular metal enclosed ring main unit is a versatile and compact solution for distribution automation, designed for efficiency and reliability. Manufactured in China, this unit features the FLN□-12 SF6 load switch as its main switch and employs air insulation throughout the cabinet. With a simple structure, flexible operation, and dependable interlocking mechanisms, it ensures easy installation and maintenance. As leading suppliers in the industry, we provide tailored technical solutions to meet diverse application needs and user specifications, The XGN□-12 unit can be equipped with high-quality FLN36-12 and FLN48-12 SF6 load switches from our factory, as well as ABB's SFG SF6 load switch. Depending on user requirements, it can also accommodate VS1, VD4/S, ISM vacuum circuit breakers, or HD4/55 SF6 circuit breakers. The load switch and circuit breaker can be operated manually or electrically, with optional electric operating mechanisms, PT, CT, FTU, and communication devices. This enables the implementation of advanced distribution automation functionalities

    Model Meaning
    SF6 Load switch
    SF6 Load Switch Model Diagram
    Modular switch cabinet
    Modular Switch Cabinet Model Diagram
    Normal Service Condition
    • Altitude: Not exceeding 2000m;
    • Ambient temperature: Minimum temperature -25℃, maximum temperature +40℃;
    • Ambient humidity: Daily average not exceeding 95%; monthly average not exceeding 90%;
    • Seismic resistance: Class 8;
    • There should be no explosive or corrosive gas in the ambient air, and no severe vibration or impact in the installation site.
    Main Purpose
    • The XGN□-12 modular metal enclosed ring main unit is suitable for power systems with a rated voltage of 12kV and rated frequency of 50Hz, and is widely used in industrial and civilian cable ring networks and power supply terminals.
    • The XGN□-12 modular metal enclosed ring main unit is particularly suitable for the following places: urban residential areas and industrial/mining enterprise power distribution, small secondary substations, switching stations, box-type substations, shopping malls, airports, subways, wind power generation, hospitals, sports venues, railways, bridges, tunnels, etc.
    Reference Standard
    GB/T 191 Packaging-Pictorial Marking for Handling of Goods (ISO 780-111997, MOD)
    GB 1985-2004 High-voltage alternating-current disconnectors and earthing switches (IEC 62271-102:2002, MOD)
    GB 3804-2004 High-voltage alternating current switches for rated voltage above 3.6 KV and less than 40.5 KV (IEC 60265-1:1998, MOD)
    GB 3906-1991 A.C. metal-enclosed switchgear for rated voltages of 3~35kV (neg IEC 60298:1990)
    GB 4208-1993 Degrees of protection provided by enclosure (IP code) (eqv IEC 60529:1989)
    GB/T 5582-1993 External insulation pollution classes of high-voltage electric power equipments (eqv IEC 507:1991)
    GB/T 6388 Transport package shipping mark
    GB 9969.1 General principles for preparation of instructions for use of industrial products
    GB/T 11022-1999 Common specifications for high-voltage switchgear and controlgear standards (eqv IEC 60694:1996)
    GB/T 11023-1989 Test method of SF6 gas tightness for high-voltage switchgear
    GB/T 13384 General specifications for packagings of mechanical and electrical products
    GB/T 14436 General principles of industrial product guarantee documents
    GB 16926-1997 High-voltage Alternating Current Switch-fuse Combinations (eqv IEC 60420:1990)
    JB/T 8754-1998 Method for Model Compilation of High Voltage Switchgear
    DL/T 404-1997 Technical Conditions for Ordering Indoor Ac High Voltage Switchgear (neq IEC 60298:1981)
    Main Technical Parameters
    Item name Unit Load switch cabinet Combination electrical cabinet Circuit breaker cabinet
    Rated voltage kV 12
    Rated frequency Hz 50/60
    Rated current A - - -
    Main busbar A 630
    Branch busbar A 630 125 (depending on fuse rated current) 630
    Rated insulation level kV - - -
    Power frequency withstand voltage (phase-phase & phase-ground) kV 42 - -
    Power frequency withstand voltage (across isolating distance) kV 48
    Power frequency withstand voltage (control & auxiliary circuit) kV 2
    Lightning impulse withstand voltage (phase-phase & phase-ground) kV 75
    Lightning impulse withstand voltage (across isolating distance) kV 85
    Rated short-time withstand current (r.m.s) kA 20 - 25
    Main circuit kA 50 - 63
    Ground circuit kA 50 80 63
    Rated peak withstand current (peak) kA - 31.5 25
    Rated short-circuit making current (peak) A - 1750 -
    Rated short-circuit breaking current A 630 - -
    Rated transfer current A 630 - 630
    Rated active load breaking current A 10 - 15
    Rated closed-loop breaking current - IP3X
    Rated cable charging breaking current Time - - -
    Protection level - 5000 5000 10000
    Mechanical life - 2000 2000 2000
    Load switch - - - -
    Ground switch - - - -
    Frequently Asked Questions (FAQ)
    What is the rated voltage of the XGN□-12 modular ring main unit?
    The rated voltage of the XGN□-12 modular metal enclosed ring main unit is 12kV, with a rated frequency of 50/60Hz.
    What are the normal environmental conditions for installing this switchgear?
    It requires an altitude not exceeding 2000m, ambient temperatures between -25℃ and +40℃, and daily average humidity below 95% (monthly average below 90%). The site must also have a seismic resistance class of 8 and be free from explosive or corrosive gases.
    Where is the XGN□-12 modular switch cabinet typically applied?
    It is highly suitable for urban residential areas, industrial and mining power distribution, small secondary substations, shopping malls, airports, subways, wind power generation stations, hospitals, railways, and tunnels.
    What is the protection level of this equipment?
    The cabinet provides an IP3X protection level to ensure safe and reliable operation in diverse industrial environments.
    What is the mechanical life of the circuit breaker cabinet compared to the load switch?
    According to the technical specifications, the circuit breaker cabinet has a mechanical life of 10,000 operations, while the load switch cabinet is rated for 5,000 operations.