0102030405
Cast Resin Dry Type Transformers from China - Safe, Maintenance-Free Solutions by Leading Suppliers and Factory
Application
SC(B)10 & SC(B)11 & SC(B)111 series three phase resin-cast dry-type distribution transformer are in conformity with standard of IEC60076 with features of low loss, compact and light weight, low noise level, clamp-proof, anti-fouling, high mechanical strength, flame resisting, strong overload ability and low partial discharge quality, they are application to power transmission and distribution system, hotel, restaurant, commercial building, stadiums, chemical plants, stations, airports, offshore drilling platforms, especially to heavy load centers and places with fire protection requirements.
Product Range
- Transformer capacity: 10kVA through 100MVA
- Temperature rise: 100℃
- Cooling type: AN & AN/AF
- Three phase frequency: 50/60HZ
- Primary voltage: 6kV through 40.5KV
- Secondary voltage: 380V&400V&415&433V or other
Technical Specification
| Type | Voltage combination | Vector group |
Loss(W) | Imped- ance % |
Dimension (L*W*H) mm |
Weight (kg) |
|||
|---|---|---|---|---|---|---|---|---|---|
| Primary (kV) |
Tapping range |
Secondary (kV) |
NO Load |
Full Load |
|||||
| SC(B)11-30/10 | 6 | ±2x2.5% | 0.4 or other |
Yyn0 or Dyn11 |
171 | 665 | 4.0 | 680*400*686 | 300 |
| SC(B)11-50/10 | 6.6 | 243 | 941 | 690*400*686 | 360 | ||||
| SC(B)11-80/10 | 7.2 | 324 | 1302 | 730*450*796 | 500 | ||||
| SC(B)11-100/10 | 10 | 360 | 1492 | 730*500*816 | 600 | ||||
| SC(B)11-125/10 | 11 | 423 | 1748 | 780*600*950 | 700 | ||||
| SC(B)11-160/10 | 13.8 | 486 | 2014 | 950*650*1124 | 850 | ||||
| SC(B)11-200/10 | 15 | 558 | 2394 | 990*650*1207 | 950 | ||||
| SC(B)11-250/10 | 20 | 648 | 2613 | 1020*650*1207 | 1100 | ||||
| SC(B)11-315/10 | 22 | 792 | 3287 | 1050*750*1320 | 1250 | ||||
| SC(B)11-400/10 | 24 | 873 | 3781 | 1100*800*1450 | 1550 | ||||
| SC(B)11-500/10 | 30 | 1044 | 4636 | 1140*800*1430 | 1850 | ||||
| SC(B)11-630/10 | 33 | 1206 | 5577 | 1250*800*1500 | 1900 | ||||
| SC(B)11-800/10 | 36 | 1368 | 6603 | 1330*800*1540 | 2200 | ||||
| SC(B)11-1000/10 | - | 1584 | 7714 | 1400*960*1640 | 2750 | ||||
| SC(B)11-1250/10 | - | 1881 | 9206 | 6.0 | 1450*960*1690 | 3300 | |||
| SC(B)11-1600/10 | - | 2205 | 11144 | 1560*960*1930 | 4000 | ||||
| SC(B)11-2000/10 | - | 2988 | 13728 | 1680*960*1930 | 4800 | ||||
| SC(B)11-2500/10 | - | 3240 | 16312 | 1720*1010*1950 | 5500 | ||||
Note: The above parameters are only the parameters of some transformers listed by our company. Any transformer capacity can be customized. (special requirement can be customized.)
Frequently Asked Questions
What standards do the SC(B) series transformers comply with?
The SC(B)10, SC(B)11, and SC(B)111 series three-phase resin-cast dry-type distribution transformers are fully in conformity with the IEC60076 standard.
What are the primary applications of these dry-type transformers?
They are ideal for power transmission and distribution systems, hotels, restaurants, commercial buildings, stadiums, chemical plants, stations, airports, offshore drilling platforms, and especially heavy load centers with strict fire protection requirements.
What cooling methods are supported?
The transformers support both AN (Air Natural) and AN/AF (Air Natural/Air Forced) cooling types depending on the application requirements.
Can the transformer capacity and specifications be customized?
Yes. While standard capacities range from 10kVA to 100MVA, any transformer capacity and special design requirements can be fully customized to meet your specific needs.
What are the key performance features of resin-cast dry-type transformers?
These transformers feature low loss, compact and light weight design, low noise level, clamp-proof and anti-fouling capabilities, high mechanical strength, flame resistance, strong overload ability, and low partial discharge.