China Pad-Mounted Transformer Suppliers | Custom Box-type Substation Factory for Efficient Power Solutions
Model meaning
Conditions of use
Product characteristics
List of fuse configuration for high voltage protection
| Rated capacity of transformer (kVA) | Low voltage side (0.4kV) rated current (A) | High voltage side (10kV) rated current (A) | Plug-in fuse capacity (A) | Backup fuse capacity (A) | Low voltage equipped main switch capacity (A) |
|---|---|---|---|---|---|
| 50 | 72.2 | 2.89 | 4 or 6 | 10 | 100 |
| 80 | 115.5 | 4.62 | 10 | 20 | 160 |
| 100 | 144.3 | 5.77 | 10 | 20 | 200 |
| 125 | 180.4 | 7.22 | 10 | 25 | 250 |
| 160 | 230.9 | 9.24 | 15 | 40 | 315 |
| 200 | 288.7 | 11.55 | 20 | 40 | 400 |
| 250 | 360.8 | 14.43 | 25 | 50 | 500 |
| 315 | 454.7 | 48.19 | 31.5 | 80 | 630 |
| 400 | 577.4 | 23.09 | 40 | 80 | 800 |
| 500 | 721.7 | 28.87 | 50 | 100 | 1000 |
| 630 | 909.3 | 36.37 | 65 | 125 | 1250 |
| 800 | 1154.7 | 46.19 | 80 | 125 | 1600 |
| 1000 | 14434 | 57.75 | 100 | 200 | 2000 |
| 1250 | 1804.2 | 72.17 | 125 | 250 | 2500 |
| 1600 | 2309.4 | 92.38 | 160 | 320 | 3200 |
Main technical parameter table
Technical parameter of 6kV and 10kV S□ series oil immersed distribution transformer
| Rated capacity kVA | Voltage combination kV | Connection group symbol | Loss kW | Off-load current % | Short circuit impedance % | Weight kg | Outline dimension mm L×W×H | Track gauge, longitudinal/ transverse | ||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| HV | LV | Off-load | Load 75% | Body weight | Oil weight | Total weight | ||||||
| 30 | 10.5 10 63 | 0.4 | Dyn11 Yzn11 Yyn0 | 0.08 | 0.63/0.6 | 1.5 | 4 | 185 | 70 | 310 | 790×660×925 | 550/400 |
| 50 | 0.1 | 0.91/0.87 | 1.3 | 255 | 85 | 395 | 820×675×1030 | 550/400 | ||||
| 63 | 0.11 | 1.09/1.04 | 1.2 | 280 | 95 | 430 | 845×690×1065 | 550/400 | ||||
| 80 | 0.13 | 1.31/1.25 | 1.2 | 320 | 100 | 480 | 865×715×1075 | 550/550 | ||||
| 100 | 0.15 | 1.58/1.5 | 1.1 | 380 | 110 | 540 | 880×720×1120 | 550/550 | ||||
| 125 | 0.17 | 1.89/1.8 | 1.1 | 444 | 115 | 600 | 910×750×1110 | 550/550 | ||||
| 160 | 0.2 | 2.31/2.2 | 1 | 510 | 130 | 690 | 910×750×1200 | 550/550 | ||||
| 200 | 0.24 | 2.73/2.6 | 1 | 640 | 150 | 840 | 1220×745×1220 | 550/550 | ||||
| 250 | 0.29 | 3.2/3.05 | 0.9 | 720 | 190 | 950 | 1240×775×1345 | 660/660 | ||||
| 315 | 0.34 | 3.83/3.65 | 0.9 | 835 | 200 | 1065 | 1230×750×1345 | 660/660 | ||||
| 400 | 0.41 | 4.52/4.3 | 0.8 | 1010 | 240 | 1255 | 1330×825×1375 | 660/660 | ||||
| 500 | 0.48 | 5.41/5.15 | 0.8 | 1170 | 260 | 1485 | 1455×915×1390 | 660/660 | ||||
| 630 | Dyn11 Yyn0 | 0.57 | 6.2 | 0.6 | 4.5 | 1375 | 320 | 1800 | 1540×920×1510 | 660/660 | ||
| 800 | 0.7 | 7.5 | 0.6 | 1620 | 365 | 2120 | 1650×1035×1555 | 820/820 | ||||
| 1000 | 0.83 | 10.3 | 0.6 | 1780 | 405 | 2450 | 1855×1235×1600 | 820/820 | ||||
| 1250 | 0.97 | 12 | 0.5 | 2065 | 560 | 2855 | 1925×1285×1680 | 820/820 | ||||
| 1600 | 1.17 | 14.5 | 0.5 | 2470 | 650 | 3400 | 2025×1355×1730 | 820/820 | ||||
| 2000 | 1.55 | 18.3 | 0.4 | 5 | 2700 | 695 | 4460 | 2190×1900×1950 | 820/820 | |||
| 2500 | 1.83 | 21.2 | 0.4 | 3230 | 870 | 5330 | 2240×1940×1980 | 1070/1070 | ||||
Note: 1. The load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 connection group, and the load loss values below the diagonal line are applicable to the Yn0 connection group.
2. The outline dimensions are for reference only during selection, and the final dimensions are subject to the product's outline drawing.
Basic structure
The box substation should be installed on a horizontal concrete platform, which should be able to withstand the weight. Due to the fact that most of the weight of the box substation is concentrated at the rear of the box containing the transformer body, the front cabinet is mostly empty and relatively light in weight. Therefore, the rear of the platform should be sturdy and able to withstand the weight of the combined transformer. Meanwhile, it is also required that the front and rear countertops be flat (generally, it is not easy to achieve flatness, so the foundation of the front cabinet can be slightly lower than that of the rear transformer body, and after being in place, it can be sealed with concrete) to ensure smooth installation of the box substation.

Frequently Asked Questions (FAQ)
The substation is designed for outdoor ambient temperatures not exceeding 40℃ and not lower than -45℃. The monthly average temperature should not exceed 30℃, and the annual average temperature should not exceed 20℃.
The substation uses air self-cooling under its standard operating conditions.
It must be installed on a horizontal concrete platform that can withstand the weight. Because the transformer body makes the rear side heavier, the rear platform must be particularly sturdy. Any unevenness can be corrected by placing the front cabinet slightly lower and sealing it with concrete after installation.
After the installation of the combined substation, there must be a gap of no less than 1.5 meters on the front of the switch to facilitate safe operation.
The grounding grid can be constructed using either 12 plated round steel or 30 x 4 galvanized flat steel. The ground wire resistance must comply with local power department regulations.