Derui, a leading factory in China, offers a comprehensive selection of distribution transformers tailored for reliable, durable, and efficient performance in utility, industrial, and commercial applications. Our liquid-filled transformers are designed to meet stringent international standards, including IEC and VDE, ensuring quality and safety. As trusted suppliers, we utilize only high-quality materials and have a dedicated team of qualified employees to implement strict quality controls in our manufacturing processes. Discover the difference with Derui's distribution transformers for all your power needs

    Characteristics
    • The transformer core is made of amorphous alloy band, no-load loss is 60% lower than that of S9 transformer and 25% lower than the stipulated value of JB/T10318.
    • The transformer adopts Ddyn11 to reduce the effect of harmonic wave to power grid and improve power supply quality.
    • The transformer adopts vacuum casting tank core, which greatly improves the reliability and stability.
    • The transformer adopts vacuum oiling method, which fully eliminates the bubbles, forming into oil tank.
    • According to years of practical experiences, our products adopt advanced technology, so the winding insulation and lightning impulse test's full-wave peak voltage is 25% higher than that of national standard, thus to make sure that the transformer can run safely and reliably.
    Core Specifications
    Width of band: 142mm, 170mm, 213mm
    Height of core aperture: 150-1000mm
    Width of core aperture: 65-500mm
    Thickness of folded core aperture: 20-180mm
    Core height: Width of band+4mm (cooling thickness epoxy resin)
    Width of band+2mm (cooling thickness of gunmetallic)
    Thickness of folded core joint: Thickness of folded core x 1.18mm
    Perimeter of outer max band is 3500mm.
    Main Parameters
    Rated capacity
    (kVA)
    Voltage combination and tapping range (kV) Vector group No-load loss
    (W)
    Load loss
    (W)
    No-load current
    (%)
    Impedance voltage
    (%)
    30 High voltage 6, 6.3, 10, 10.5, 11
    High voltage tapping range ±5±2×2.5
    Low voltage 0.4
    Dyn11 33 600 1.70 4.0
    50 43 870 1.30
    63 50 1040 1.20
    80 60 1250 1.10
    100 75 1500 1.00
    125 85 1800 0.90
    160 100 2200 0.70
    200 120 2600 0.70
    250 140 3050 0.70
    315 170 3650 0.50
    400 200 4300 0.50
    500 240 5160 0.50
    630 320 6200 0.30
    800 380 7500 0.30
    1000 450 10300 0.30
    1250 530 12000 0.20 4.5
    1600 630 14500 0.20
    2000 750 17400 0.20
    2500 900 20200 0.20 5
    Type SH16-M Technical Parameters
    Type Rated capacity
    (kVA)
    Voltage combination (kV) Vector group No-load loss
    (W)
    Load loss
    (W)
    No-load current
    (%)
    Impedance voltage
    (%)
    Outline dimensions (mm)
    L H B
    Installation center distance
    (L1xL2) (mm)
    Weight of oil
    (kg)
    Total weight
    (kg)
    SH16-M-50/10 50 High voltage 6, 6.3, 10, 10.5, 11
    High voltage tapping range ±5±2×2.5
    Low voltage 0.4
    Dyn11 38 870 0.9 4.0 950 1040 620 400x650xΦ14 160 680
    SH16-M-100/10 100 58 1500 0.7 4.0 1060 1070 770 400x650xΦ14 190 890
    SH16-M-160/10 160 78 2200 0.5 4.0 1050 1150 930 400x650xΦ14 230 1190
    SH16-M-200/10 200 90 2600 0.5 4.0 1110 1170 930 550x650xΦ19 270 1300
    SH16-M-250/10 250 110 3050 0.5 4.0 1180 1180 1010 550x650xΦ19 300 1460
    SH16-M-315/10 315 130 3650 0.4 4.0 1180 1180 1010 550x650xΦ19 240 1400
    SH16-M-400/10 400 160 4300 0.4 4.0 1200 1180 1010 550x650xΦ19 280 1660
    SH16-M-500/10 500 190 5150 0.4 4.0 1270 1300 1160 660x700xΦ19 300 1950
    SH16-M-630/10 630 230 6200 0.3 4.5 1450 1330 1240 820x700xΦ19 480 2450
    SH16-M-800/10 800 280 7500 0.3 4.5 1520 1460 1380 820x700xΦ19 520 2900
    SH16-M-1000/10 1000 330 10300 0.3 4.5 1720 1510 1460 820x700xΦ19 680 3500
    SH16-M-1250/10 1250 390 12000 0.2 4.5 1760 1650 1330 820x700xΦ19 800 3980
    SH16-M-1600/10 1600 470 14500 0.2 4.5 1980 1710 1380 820x700xΦ19 850 5350
    SH16-M-2000/10 2000 570 17400 0.2 5.0 2085 1790 1545 820x700xΦ19 1010 6350
    SH16-M-2500/10 2500 680 20200 0.2 5.0 2400 2350 1500 820x700xΦ19 1050 8200
    Voltage Class & Power Frequency Withstand Voltage
    Voltage class
    (kV)
    Highest voltage for equipment Effective value of
    Maximum phase voltage (kV)
    Rated short-time power frequency withstand voltage Effective value of
    Power-frequency withstand voltage (kV/min)
    Rated lightning impulse withstand voltage Full wave peak value of rated voltage
    Lightning impulse withstand voltage (kV)
    0.6 ≤1.1 3 —
    3 3.5 18 40
    6 6.9 25 60
    10 11.5 35 75
    20 23 50 125
    Frequently Asked Questions
    Q1: What are the energy-saving benefits of using an amorphous alloy core in these transformers?
    The amorphous alloy band core significantly reduces core losses. Specifically, the no-load loss is 60% lower than that of standard S9 transformers and 25% lower than the value specified by the JB/T10318 standard.
    Q2: How does the Ddyn11 vector group configuration improve grid performance?
    By adopting the Ddyn11 vector group, the transformer effectively minimizes the impact of harmonic waves on the power grid, resulting in a cleaner and higher quality power supply.
    Q3: What is the benefit of the vacuum casting tank core and vacuum oiling process?
    The vacuum casting tank core greatly enhances structural reliability and operation stability. Additionally, the vacuum oiling method completely eliminates air bubbles during the oil tank formation, preventing insulation degradation.
    Q4: How do the winding insulation and impulse test parameters compare to national standards?
    Thanks to advanced manufacturing technologies, the full-wave peak voltage during winding insulation and lightning impulse tests is 25% higher than the national standard requirement, ensuring safe and reliable operations under high electrical stress.
    Q5: What core aperture heights and widths are available for customization?
    The core aperture height ranges from 150mm to 1000mm, while the core aperture width ranges from 65mm to 500mm, allowing for flexible configurations based on specifications.
    Q6: What is the rated lightning impulse withstand voltage for a 10kV voltage class transformer?
    For the 10kV voltage class, the transformer is designed to withstand a rated lightning impulse full wave peak voltage of up to 75kV, with a power-frequency withstand voltage of 35kV/min.