China HXGN-12 Ring Main Unit - Reliable Suppliers and Factory for 12kV AC Metal Enclosed Solutions
Model Meaning
Normal Service Condition
- The upper limit of ambient temperature is +40℃, and the lower limit is -25℃;
- Altitude should not exceed 2000m;
- The daily average relative humidity of the air should not exceed 95%, and the monthly average should not exceed 90%; The daily average value of water vapor shall not exceed 2.2×10-3Mpa, and the monthly average value shall not exceed 1.8×10-3Mpa;
- The ambient air should not be significantly polluted by corrosive or flammable gas, water vapor, etc;
- No frequent severe vibration.
Main Technical Parameters
| Item name | Unit | Argument | |
| Rated voltage/maximum operating voltage | kV | 10/12 | |
| Rated current | A | 630 | |
| Main busbar current | Incoming cabinet | A | 630 |
| Outgoing cabinet | 125 | ||
| Rated short-time withstand current | kA | 20 | |
| Rated short-circuit duration | s | 4 | |
| Rated peak withstand current | kA | 50 | |
| Rated short-circuit making current | kA | 50 | |
| Rated active load breaking current | A | 630 | |
| Closed-loop breaking current | A | 630 | |
| Rated cable charging current | kA | 20 | |
| Rated short-time withstand current of ground switch | kA | 20 | |
| Rated short-circuit duration of ground switch | s | 4(2) | |
| Rated peak withstand current of ground switch | kA | 50 | |
| Rated short-circuit making current of ground switch | kA | 50 | |
| 1min rated power frequency withstand voltage | Phase-phase, phase-ground, isolating distance of vacuum load switch | kV | 42 |
| Isolating distance of isolation switch | 48 | ||
| Rated lightning impulse withstand voltage | Phase-phase, phase-ground, isolating distance of vacuum load switch | kV | 75 |
| Isolating distance of isolation switch | 85 | ||
| Mechanical life | Vacuum load switch | Time | 10000 |
| Ground switch(knife), isolation switch(knife) | 2000 | ||
| Take-over current | A | 3150 | |
Technical Requirement
The ring main unit equipped with FZN □-12/630 vacuum load switch should be able to meet all the corresponding technical requirements of FZN-12/630 vacuum load switch.
This ring main unit is insulated with air and mainly equipped with FZN □-12/630 vacuum load switch. The main solutions include incoming and outgoing cabinets.
The main circuit of the cabinet has one FZN□-12/630 vacuum load switch, which is equipped with isolation knife and ground knife if necessary. The above three are installed on one frame and interlocked with each other. Therefore, it can achieve the operation of connecting the busbar, isolating and grounding three workstations, and the cabinet can also be flexibly equipped with CT, PT and other components.
The main circuit inside the cabinet consists of a FZRN □-12/T200 vacuum load switch, a fuse with an striker (acting as an isolation switch) and a ground knife, which can also achieve three-station operation. The cabinet can also be flexibly equipped with components such as CT/PT and YH series lightning arrester, so sometimes the metering cabinet can be omitted. Both the incoming and outgoing cabinets are equipped with insulation protective partitions interlocked with the ground switch. The switches, partitions and cabinet doors inside the cabinet are mechanically interlocked and meet the "five prevention" requirement. The protection level of the cabinet shell is IP2X.
Use of Product
◆ Usage Notice: Please strictly follow the following steps, otherwise it may cause damage.
Operation sequence of load switch
Power outage operation sequence
Power transmission operation sequence
Fault Handling
If the fasteners of the ring main unit become loose, the mechanical parts are poorly lubricated, and the vacuum degree of the vacuum extinguishing chamber decreases during operation, methods such as tightening, adding lubricant and applying pressure resistance should be used to check and eliminate the above faults after power outage.
Outline and Installation Dimension
Frequently Asked Questions (FAQ)
What are the normal ambient temperature operating limits for this ring main unit?
The normal ambient operating temperature limit has an upper limit of +40℃ and a lower limit of -25℃.
What is the maximum installation altitude for this device?
The installation altitude for this ring main unit should not exceed 2000 meters above sea level.
How does the Incoming Cabinet Solution achieve workstation interlocking?
The main circuit of the incoming cabinet features one FZN□-12/630 vacuum load switch, which can be configured with an isolation knife and ground knife on a single frame. These components are mechanically interlocked to safely manage busbar connection, isolation, and grounding operations.
What are the safety protection levels and interlocking features of the cabinet shell?
The cabinet shell is built to a protection level of IP2X. The switches, insulation protective partitions, and cabinet doors are mechanically interlocked to completely fulfill the "five prevention" safety standards.
What maintenance procedure should be followed if faults like loose parts or poor lubrication occur?
In case of loose fasteners, poor mechanical lubrication, or a reduction in vacuum levels inside the extinguishing chamber, maintenance should only be conducted during a scheduled power outage by tightening, adding lubricant, and applying pressure resistance checks.