Leave Your Message
12KV Ring Main Unit XGN-12 from China Factory - Reliable Suppliers for Distribution Automation Solutions
Hot Products

12KV Ring Main Unit XGN-12 from China Factory - Reliable Suppliers for Distribution Automation Solutions

,

The XGN□-12 modular metal enclosed ring main unit is a highly compact and expandable solution for distribution automation, designed by a leading China factory. Utilizing the advanced FLN□-12 SF6 load switch as its primary switch, this unit employs reliable air insulation throughout its construction. Key features include a simple structure, flexible operation, dependable interlocking mechanisms, and easy installation. As a top supplier in the industry, we offer tailored technical solutions to meet various application requirements and user specifications.

,

The XGN□-12's main switch is compatible with our FLN36-12 and FLN48-12 SF6 load switches, as well as SFG SF6 load switches manufactured by ABB. Additionally, we can install VS1, VD4/S, ISM vacuum circuit breakers, or HD4/55 SF6 circuit breakers according to your specific needs. Both load switches and circuit breakers can be operated either manually or electrically, providing options such as electric operating mechanisms, PT, CT, FTU, and communication devices, thereby ensuring effective distribution automation functionality. Choose us as your trusted supplier for innovative solutions in the electrical distribution sector.

,

,

    Model meaning

    SF6 Load switch

    SF6 Load switch Model Meaning

    Modular switch cabinet

    Modular switch cabinet Model Meaning
    Normal service condition
    • Altitude: not exceeding 2000m;
    • Ambient temperature: minimum temperature -25℃, maximum temperature +40℃;
    • Ambient humidity: daily average not exceeding 95%; monthly average not exceeding 90%;
    • Seismic resistance: 8;
    There should be no explosive or corrosive gas in the ambient air, and no severe vibration or impact in the installation site.
    Main purpose
    • The XGN□-12 modular metal enclosed ring main unit is suitable for power system with rated voltage of 12kV and rated frequency of 50Hz, and is widely used in industrial and civilian cable ring network and power supply terminal.
    • The XGN □-12 modular metal enclosed ring main unit is particularly suitable for the following places: urban residential area and industrial and mining enterprise power distribution, small secondary substation, switching station, box-type substation, shopping mall, airport, subway, wind power generation, hospital, sports venue, railway, bridge, tunnel, etc.
    Reference standard
    GB/T191 Packaging-Pictorial Marking for Handling of Goods (ISO 780-111997, MOD)
    GB1985-2004 High-voltage alternating-current disconnectors and earthing switches (IEC 62271-102:2002, MOD)
    GB 3804-2004 High-voltage alternating current switches for rated voltage above 3.6 KV and less than 40.5 KV (IEC 60265-1:1998, MOD)
    GB 3906-1991 A.C. metal-enclosed switchgear for rated voltages of 3~35kV (neq IEC 60298:1990)
    GB 4208-1993 Degrees of protection provided by enclosure (IP code) (eqv IEC 60529:1989)
    GB/T 5582-1993 External insulation pollution classes of high-voltage electric power equipments (eqv IEC 507:1991)
    GB/T 6388 Transport package shipping mark
    GB 9969.1 General principles for preparation of instructions for use of industrial products
    GB/T11022-1999 Common specifications for high-voltage switchgear and controlgear standards (eqv IEC 60694:1996)
    GB/T 11023-1989 Test method of SF6 gas tightness for high-voltage switchgear
    GB/T13384 General specifications for packagings of mechanical and electrical products
    GB/T14436 General principles of industrial product guarantee documents
    GB16926-1997 High-voltage Alternating Current Switch-fuse Combinations (eqv IEC 60420:1990)
    JB/T 8754-1998 Method for Model Compilation of High Voltage Switchgear
    DL/T 404-1997 Technical Conditions for Ordering Indoor Ac High Voltage Switchgear (neq IEC 60298:1981)
    Main technical parameters
    Item name Unit Load switch cabinet Combination electrical cabinet Circuit breaker cabinet
    Rated voltage kV 12
    Rated frequency Hz 50/60
    Rated current A      
    Main busbar A 630
    Branch busbar A 630 125 (depending on the rated current of the fuse) 630
    Rated insulation level kV      
    Power frequency withstand voltage (phase-phase and phase-ground) kV 42    
    Power frequency withstand voltage (across isolating distance) kV 48
    Power frequency withstand voltage (control and auxiliary circuit) kV 2
    Lightning impulse withstand voltage (phase-phase and phase-ground) kV 75
    Lightning impulse withstand voltage (across isolating distance) kV 85
    Rated short-time withstand current (r.m.s) kA 20 - 25
    Main circuit kA 50 - 63
    Ground circuit kA 50 80 63
    Rated peak withstand current (peak) kA   31.5 25
    Rated short-circuit making current (peak) A - 1750  
    Rated short-circuit breaking current A 630   -
    Rated transfer current A 630 - 630
    Rated active load breaking current A 10 - 15
    Rated closed-loop breaking current   IP3X
    Rated cable charging breaking current Time      
    Protection level   5000 5000 10000
    Mechanical life   2000 2000 2000
    Load switch        
    Ground switch        
    Frequently Asked Questions
    1. What are the installation altitude limitations for the XGN□-12 ring main unit?
    The normal service condition for the installation altitude of the XGN□-12 modular metal enclosed ring main unit should not exceed 2000 meters above sea level.
    2. What are the ambient temperature requirements for operating this switchgear?
    The switchgear is designed to operate within an ambient temperature range from a minimum of -25℃ to a maximum of +40℃.
    3. Where is the XGN□-12 modular ring main unit typically used?
    It is highly suitable for urban residential power distribution, industrial and mining enterprise networks, small secondary substations, switching stations, airports, subways, wind power generation, hospitals, and various sports venues.
    4. What is the protection level provided by the switchgear enclosure?
    Based on the technical specifications, the protection level provided by the metal enclosure of the switchgear system is rated at IP3X.
    5. What is the mechanical life of the circuit breaker cabinet compared to the load switch?
    The circuit breaker cabinet is rated for a mechanical life of 10,000 operations, whereas both the load switch cabinet and combination electrical cabinet are rated for 5,000 operations.