The KYN28-24 indoor AC metal armored removable switchgear (hereafter referred to as switchgear) is designed for three-phase power systems operating at a frequency of 50Hz and a rated voltage of 24kV. This reliable equipment is ideal for use in power plants, substations, industrial and mining enterprises, and high-rise buildings, where it plays a crucial role in receiving and distributing electric energy, as well as enabling circuit control, protection, and monitoring.

Manufactured in China, this switchgear incorporates a range of safety features to prevent operational missteps, including mechanisms that prevent the trolley from moving while loaded, restrict the ground switch from closing the circuit breaker when it is in a closed position, and ensure the live ground switch remains secure. It also provides safeguards against accidental access to live compartments.

Equipped with advanced control and protection components in its secondary circuit, this switchgear features a bus that uses heat shrinkable insulation materials or epoxy coating insulation for optimized electrode shaping. With its compact structure, the cabinet embodies cutting-edge technology, delivering stable performance, thoughtful design, ease of use, and exceptional safety and reliability. As a trusted product from experienced suppliers and a reputable factory, the KYN28-24 switchgear is your go-to solution for modern electric distribution needs.

    Model Meaning

    20241106-德锐电气(2024版)(中英文)最终定稿版-84.jpg

    Product Standard

    • GB311.1 Insulation co-ordination-Part1:Definitions,principles and rules
    • GB1984 High-voltage alternatiing-current circuit-breakers
    • GB3906 Alternating-current metal-enclosed switchgear and controlgear for rated voltages above 3.6kVand up to and including 40.5kV
    • GB/T11022 Common specifications for high-voltage alternating-current switchgear and controlgear standards
    • Common specifications for high-voltageswitchgear and controlgear standards
    • IEC62271-20:2003 High-voltage switchgear and controlgear-Part 200:AC metal-enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 52kV

    Conditions of Use

    • Altitude: ≤1000m;
    • Ambient temperature: upper limit of ambient air temperature +40℃, lower limit -15℃;
    • Relative humidity: The daily average relative humidity shall not exceed 95%; monthly average relative humidity shall not exceed 90%;
    • Seismic intensity: The seismic intensity does not exceed 8 degrees;
    • It's not suitable for places with obvious pollution such as corrosive or flammable gas and water vapor, etc.
    • When the above normal service conditions are not met, the user can negotiate with the manufacturer.

    Product Characteristics

    • The switchgear is designed with complete metal armor and fully enclosed structure.
    • The interior of the switchgear is divided into four independent compartments: circuit breaker room, busbar room, cable room and relay instrument room. Each functional unit is sealed with metal plates and equipped with independent pressure release channel and release door.
    • The switch cabinet body is made of high-quality cold-rolled steel plate processed by CNC sheet metal forming, and connected by high-strength bolts, nuts and rivet nuts. The surface of the components is sprayed or galvanized; it can be equipped with VS1(ZN63A) vacuum circuit breaker and ABB's VD4 and Schneider's HVX series circuit breakers to meet the needs of different users.
    • The switchgear can perform circuit breaker opening and closing, moving-in/out, and ground switch opening and closing with the cabinet door closed.
    • The switchgear is designed to prevent misoperation of circuit breaker, prevent pushing trolley with load, prevent ground switch from transmitting power at the grounding position, and prevent accidental entry into live compartments, meeting the "five prevention" functions.
    • The convenient door panel observation window of the switchgear allows for viewing of the circuit breaker's on/off status, trolley position, energy storage position, and ground switch's on/off status.
    • The switchgear trolley has good interchangeability, and the secondary wires are located in spacious cable tray, which are beautiful and easy to find. The primary cable connection is convenient.
    • The protection level of the outer shell is IP4X, while the protection level is IP2X between small rooms and when the circuit breaker door is open. The installation and maintenance of the cabinet can be carried out on the front or back. The switchgear can not only be installed in a face-to-face or back-to-back double row arrangement, but also can be installed against the wall according to specific project requirements, which saves floor space and improves the safety and flexibility of the switchgear.

    Schematic Diagram of Switchgear Structure

    KYN28 switchgear structure diagram 1
    KYN28 switchgear structure diagram 2

    Technical Parameter

    Item Unit Argument
    Rated voltage kV 24
    Rated frequency Hz 50/60
    Rated insulation level 1min power frequency withstand voltage(effective value) kV Phase-phase, phase-ground: 65 Isolating distance: 79
    Lightning impulse withstand voltage(peak value) kV Phase-phase, phase-ground: 125 Isolating distance: 145
    Power frequency withstand voltage of auxiliary control circuit V 2000
    Rated current A 63,012,501,600,200,000,000,000
    Rated short-circuit breaking current KA 20 25 31.5
    Rated short-circuit making current(peak) KA 50 63 80
    Rated short-time withstand current(4s) KA 20 25 31.5
    Rated peak withstand current KA 50 63 80
    Rated voltage of auxiliary control circuit V 110V/220V DC or AC 110V/220V
    Protection level   IP4X / IP2X
    Outline dimension (Width×Depth×Height) mm 800×1810×2430 / 1000×1810×2430
    Weight kg 840~1440

    Frequently Asked Questions

    What standards does this switchgear comply with?
    The switchgear is designed and manufactured in strict compliance with major industry standards, including GB311.1, GB1984, GB3906, GB/T11022, and IEC62271-20:2003.
    What are the environmental requirements for installation?
    It is suitable for altitudes up to 1000m, ambient temperatures between -15℃ and +40℃, and daily relative humidity under 95% (monthly under 90%). It should not be installed in locations with high concentrations of corrosive or flammable gases, or excessive water vapor.
    Which brands of circuit breakers are compatible with this cabinet?
    The unit can be flexibly configured with domestic VS1 (ZN63A) vacuum circuit breakers, as well as premium international options like ABB's VD4 and Schneider's HVX series circuit breakers.
    What safety mechanisms are built into the design?
    It features complete metal armor, a fully enclosed partition structure, and independent pressure release doors for each compartment. It also incorporates a comprehensive "five prevention" system to prevent accidental operations, such as moving the trolley under load or entering live compartments.
    What is the enclosure protection rating (IP code)?
    The outer enclosure features an IP4X protection level. When the circuit breaker door is open or between internal compartments, the protection level is IP2X.
    Can the switchgear be installed directly against a wall?