DR-GTXGN-12 Solid Insulation Ring Main Unit - Reliable Power Distribution Solution from China Suppliers & Factory
Hot Products

DR-GTXGN-12 Solid Insulation Ring Main Unit - Reliable Power Distribution Solution from China Suppliers & Factory

The DR-GTXGN-12 is a cutting-edge solid-insulated ring main unit switchgear designed by our factory in China. This innovative, environmentally-friendly switchgear is fully sealed, ensuring that each live component and switch is enclosed in a durable epoxy plastic shell, completely free of SF6 gas. Its robust design guarantees high reliability and safety in operation, making it a maintenance-free solution suitable for various applications.

Utilizing solid insulation material as its primary insulation medium, the DR-GTXGN-12 includes essential components such as conductive connectors, isolation switches, grounding switches, and both main and branch bus systems. These components can be encapsulated into a completely insulated and sealed module, either individually or in combination, allowing for further customization and expansion.

This ring main unit is specifically engineered for 12kV, 50Hz three-phase AC power distribution systems, making it ideal for both ring main and terminal power distribution. It can be efficiently deployed in diverse settings including industrial and mining enterprises, residential complexes, educational institutions, parks, and compact substations, effectively controlling and protecting power distribution transformers. As a result, the DR-GTXGN-12 is perfectly suited for both indoor and outdoor power distribution automation, showcasing the quality and innovation that China suppliers are known for.

    Model and meaning

    20241106-德锐电气(2024版)(中英文)最终定稿版-37.jpg

    Work environmental conditions

    It is ideal for indoor or outdoor use.
    Ambient air temperature: Indoor -10° C~+25° C, outdoor -60° C~+60° C.
    Relative air humidity: Daily average is no more than 95%, monthly average is no more than 90%.
    Altitude is no more than 3000m.
    Ambient air is free from any pollution of dust, water vapor, salt fog, corrosive gases or flammable gases: the outdoor type can be used in severe environmental conditions.
    No severe vibration in the area to install, and the earthquake intensity is no more than 8 ML.

    When the work environmental conditions can not meet the requirements above, the user shall consult with the manufacturer.

    Safety and protection

    Insulation knife visual cutout

    With an obvious visible cutout window in front of the cabinet, it is convenient and safe for the personnel on site to check the three positions such as the insulation closing position, insulation breaking position and grounding closing position and confirm the insulation knife position.

    Pressure relief design

    Internal arcing pressure valve; when any arcing occurs in the product, the pressure will be relieved from the pressure relief valve and the arcing will be discharged to the cable trench to prevent any injury to the operator.

    Environment-friendly and green

    With environment-friendly materials in design, SF6 gas isn’t used as the arc extinguishing medium and insulation, without pollution to the environment, the primary circuit has minimum-contact design to ensure low energy consumption in operation.

    Execution standards

    IEC62271-1-2007 “High-voltage switchgear and controlgear Part-1 Common specifications”
    IEC620071-200-2003 “AC metal-enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 52kV”
    GB3906-2006 “Alternating-current metal-enclosed switchgear and controlgear for rated voltage above 3.6kV and up to and including 40.5kV”
    GB/T11022-2011 “Common specification for high-voltage switchgear and controlgear standards”
    GB1984-2014 “High-voltage alternating-current circuit-breakers”
    GB1985-2014 “High-voltage alternating-current disconnectors and earthing switches”
    GB3804-2004 “High-voltage alternating-current switches for rated voltage above 3.6kV and less than 40.5kV”
    DL/T404-2007 “Alternating-current metal-enclosed switchgear and controlgear for rated voltages above 3.6kV and up to and including 40.5kV”
    DL/T593-2016 “Common specification for high-voltage switchgear and controlgear standards”
    Q/GDW730-2012 “Specifications for 12kV solid-insulated ring main units”
    DL/T402-2016 “High-voltage alternating-current circuit-breakers”
    20241106-德锐电气(2024版)(中英文)最终定稿版-38.jpg
    20241106-德锐电气(2024版)(中英文)最终定稿版-38-1.jpg

    Main technical parameters (whole switchgear)

    Name Unit Parameter
    Rated voltage kV 12
    Rated current A 630
    Rated short-time withstand current (4s) kA 25
    Rated peak withstand current kA 50
    Rated short-circuit closing current (peak) kA 50
    Rated active load breaking current A 630
    Rated closed loop breaking current A 630
    Rated cable charge breaking current A 10
    Rated breaking transfer current of combined appliances A 3700
    1min power frequency withstand voltage Phase-to-phase, phase-to-ground, vacuum breaking kV 42
    Insulation breaking kV 48
    Lightning impact withstand voltage Phase-to-phase, phase-to-ground, vacuum breaking kV 75
    Insulation breaking kV 85
    Mechanical life Circuit breaker Time 10000
    Insulation knife, grounding knife Time 3000
    Protection grade   IP4X
    Shell protection grade   IP4X
    Partial discharge pc ≤20 (Measured at 1.2Ur)

    Frequently Asked Questions (FAQ)

    What are the ambient temperature limits for this switchgear?

    The switchgear is designed to operate in ambient temperatures ranging from -10°C to +25°C for indoor use, and from -60°C to +60°C for outdoor applications.

    Does the system use SF6 gas for insulation?

    No, this environment-friendly design does not use SF6 gas as the arc extinguishing medium or insulation. It utilizes green materials and features a minimum-contact primary circuit design to guarantee low energy consumption and zero environmental pollution.

    What is the maximum installation altitude for this equipment?

    The standard maximum installation altitude is 3000 meters. If your working environmental conditions exceed this limit, please consult directly with the manufacturer.

    How does the pressure relief design protect operators?

    The switchgear is built with an internal arcing pressure valve. In the event of an internal arc fault, the built-up pressure is safely discharged through the valve into the cable trench, keeping operators on site protected from injury.

    What is the mechanical life of the circuit breaker and insulation knife?

    The circuit breaker has a mechanical life of 10,000 operations, while the insulation knife and grounding knife are rated for 3,000 operations.

    Which international and national standards are followed?

    This equipment complies with several prominent standards, including IEC 62271-1-2007, IEC 620071-200-2003, GB 3906-2006, GB/T 11022-2011, and DL/T 404-2007, ensuring it meets strict global and regional performance criteria.