China GCS Low Voltage Withdrawable Switchgear - High Performance from Trusted Suppliers and Factory
Hot Products

China GCS Low Voltage Withdrawable Switchgear - High Performance from Trusted Suppliers and Factory

The GCS type low-voltage withdrawable switchgear is an advanced product developed by a collaborative team from China’s former Ministry of Electric Power Industry and the Ministry of Machinery Industry in the 1990s. Designed to meet national requirements, this switchgear features high technical performance and is capable of keeping pace with the evolving electricity market. It competes effectively with imported products, gaining recognition and preference among numerous electricity users, This switchgear is compatible with three-phase four-wire and three-phase five-wire power systems, operating at a frequency of 50Hz and a rated voltage of 380V (400V), supporting rated currents of up to 4000A. It is extensively utilized in various sectors, including power plants, substations, industrial and mining enterprises, commercial buildings, hotels, airports, and docks, facilitating energy distribution, conversion, control, and reactive power compensation, The GCS switchgear can function both as a power center (PC) and a motor control center (MCC) and is available in mixed fixed and withdrawable cabinet designs to cater to diverse power supply and distribution requirements. With high breaking capacity, excellent dynamic and thermal stability, innovative design, comprehensive electrical solutions, and a high protection level, this switchgear presents itself as an ideal choice for those seeking quality products from reliable China suppliers and factories

    Model meaning

    20241106-德锐电气(2024版)(中英文)最终定稿版-70.jpg

    Conditions of use

    Altitude

    ≤ 2000m

    Air temperature

    Upper limit: +40℃, lower limit: -5℃. The average temperature within 24 hours should not exceed +35℃. Minimum storage/transportation temperature: -30℃.

    Relative humidity

    Does not exceed 50% at +40℃. Higher relative humidity is allowable at lower temperatures (e.g. 90% at +20℃). Occasional condensation due to temperature changes should be considered.

    Installation location

    Inclination of the vertical plane should not exceed 5°. Install in a place free from severe vibration, impact, or medium sufficient to corrode electrical components.

    Note: When the above normal service conditions cannot meet the usage requirements, it shall be negotiated between the user and the manufacturer.

    Product characteristics

    Strong commonality & Flexible assembly

    Fully assembled combination structure. Side installation holes of 20mm and 100mm modules (φ 9.2mm) make internal installation flexible and convenient.

    Compartment isolation

    Divided into functional unit room, busbar room, and cable room. Areas are strictly separated by grounded metal plates or flame-retardant plastic plates to ensure safety.

    High durability & Grounding

    All internal structural components are galvanized and passivated. Panels are made of high-quality cold-rolled steel plates processed by CNC, with acid washing, phosphating, and electrostatic spraying.

    Reliable draw-out interlock

    Five draw-out positions with mechanical interlocks. Units can only be moved when the switch is open. Operating handles can be padlocked in the open position.

    Busbar & Cable Arrangement

    The horizontal main busbar is flatly arranged at the back of the cabinet to resist high short-circuit power. Vertical busbars are assembled in insulated functional boards to prevent phase discharge. Cable compartments allow convenient entry and exit from both top and bottom.

    Technical parameter

    Parameter Name Value / Specification
    Rated insulation voltage (V) AC660
    Rated working voltage (V) AC380V (AC400)
    Rated current of horizontal busbar (A) ≤4000A
    Rated current of vertical busbar (A) 1000A
    Maximum current of draw-out circuit (A) 400A
    Rated frequency (Hz) 50 (60)
    Peak withstand current of horizontal busbar (kA) 105, 176
    Short time withstand current of horizontal busbar (kA/1S) 50, 80
    Peak withstand current of vertical busbar (kA) 105
    Short time withstand current of vertical busbar (kA/1S) 50
    Rated power frequency withstand voltage (V/1min) 2500
    Secondary power frequency withstand voltage (V/1min) 2500
    Enclosure protection level IP40
    Enclosure dimension (mm) Width 600(800,1000) × Depth 800(1000) × Height 2200
    Effective height of functional unit (mm) 1760

    Switchgear and draw-out types

    According to the purpose, it can be classified into: incoming cabinet, bus-tie cabinet, feeder cabinet (motor centralized control cabinet, lighting distribution cabinet), and reactive power compensation cabinet.

    According to the incoming method, it can be classified into four types: upper incoming & upper outgoing, upper incoming & lower outgoing, lower incoming & upper outgoing, and lower incoming & lower outgoing.

    There are five height specifications for the draw-out units, based on a basic unit height of 160mm: 1/2 unit, 1 unit, 3/2 unit, 2 unit, and 3 unit. The maximum draw-out circuit current is 400A or below.

    Outline and installation dimension of switchgear

    Name of switchgear Width (W) Depth (D) Height (H) Cable outlet (FXG)
    Incoming cabinet 600, 800, 1000 800, 1000 2200 -
    Bus-tie cabinet 800, 1000 -
    Feeder cabinet 800, 1000 200×400, 400×400
    Draw-out cabinet 800, 1000 200×350, 400×350
    Compensation cabinet 800, 1000 -
    Note: The above sizes are recommended. Users with special size requirements can negotiate with our company.
    20241106-德锐电气(2024版)(中英文)最终定稿版-71.jpg
    20241106-德锐电气(2024版)(中英文)最终定稿版-71-1.jpg

    Mounting dimension

    20241106-德锐电气(2024版)(中英文)最终定稿版-72.jpg

    Installation diagram

    20241106-德锐电气(2024版)(中英文)最终定稿版-72-1.jpg

    Frequently Asked Questions (FAQ)

    What is the maximum altitude limit for using this switchgear?
    The normal altitude for installing and operating this switchgear should be less than or equal to 2000 meters.
    What are the ambient air temperature limits for normal operations?
    The upper limit of ambient air temperature is +40℃, and the lower limit is -5℃. The average temperature within 24 hours should not exceed +35℃. Under storage and transport conditions, the minimum allowable temperature is -30℃.
    What is the protection level of the switchgear enclosure?
    The enclosure protection level of this switchgear is rated at IP40.
    Can draw-out units of the same specification be interchanged?
    Yes, functional draw-out units of the same specification can be easily interchanged. Each draw-out unit corresponds to a maximum of 36 pairs of auxiliary contacts to meet various control requirements.
    How does the mechanical interlock on the draw-out unit function?
    The draw-out unit can only be pulled out or inserted when the switch is in the open state. It cannot be moved while the switch is closed. Additionally, the operating mechanism handle can be locked in the open position with a padlock to prevent unauthorized operation.
    What height options are available for the draw-out units?
    There are five specifications for draw-out unit height, all based on a basic unit height of 160mm: 1/2 unit, 1 unit, 3/2 unit, 2 unit, and 3 unit.