Introducing the KYN61-40.5 armored removable AC metal enclosed switchgear, a premier solution designed for three-phase AC 50Hz 40.5kV power systems. This switchgear is ideal for distribution rooms in power plants, substations, and industrial and mining enterprises, effectively receiving and distributing electrical energy. With robust functions for control, protection, and monitoring of circuits, this product stands out in both general power systems and environments requiring frequent operations, Manufactured with an innovative assembled structure, our switchgear not only enhances aesthetic quality but also improves manufacturing precision. The busbar features advanced insulation techniques, utilizing heat shrinkable insulation materials or epoxy coatings to optimize electrode shapes. The compact design of the cabinet is complemented by comprehensive five prevention functions, ensuring reliable operation and safety, Complying with relevant standards such as GB3096, GB/T11022, IEC60298, and DT/L404, this switchgear represents the highest industry standards. As a trusted China supplier and factory, we are committed to delivering high-quality products tailored to meet the needs of modern power systems. Upgrade your electrical distribution with our KYN61-40.5 switchgear today!

    Model Meaning

    Model Meaning Diagram

    Conditions of Use

    • Altitude: ≤1000m;
    • Ambient temperature: Upper limit of ambient air temperature +40℃, lower limit -15℃;
    • Relative humidity: The daily average relative humidity shall not exceed 95%; monthly average relative humidity shall not exceed 90%;
    • Seismic intensity: The seismic intensity does not exceed 8 degrees;
    • It's not suitable for places with obvious pollution such as corrosive or flammable gas and water vapor, etc.
    • When the above normal service conditions are not met, the user can negotiate with the manufacturer.

    Product Characteristics

    • The switchgear is designed with complete metal armor and fully enclosed structure.
    • The interior of the switchgear is divided into four independent compartments: circuit breaker room, busbar room, cable room and relay instrument room. Each functional unit is sealed with metal plates and equipped with independent pressure release channel and release door.
    • The switch cabinet body is made of high-quality cold-rolled steel plate processed by CNC sheet metal forming, and connected by high-strength bolts, nuts and rivet nuts. The surface of the components is sprayed or galvanized; it can be equipped with ZN85A vacuum circuit breaker and French Schneider's SF1, SF2 type and Alstom FP series SF6 circuit breaker to meet the needs of different users.
    • The switchgear can perform circuit breaker opening and closing, moving-in/out, and ground switch opening and closing with the cabinet door closed.
    • The switchgear is designed to prevent misoperation of circuit breaker, prevent pushing trolley with load, prevent ground switch from transmitting power at the grounding position, and prevent accidental entry into live compartments, meeting the "five prevention" functions.
    • The convenient door panel observation window of the switchgear allows for viewing of the circuit breaker's on/off status, trolley position, energy storage position, and ground switch's on/off status.
    • The switchgear trolley has good interchangeability, and the secondary wires are located in spacious cable tray, which are beautiful and easy to find. The primary cable connection is convenient.
    • The protection level of the outer shell is IP4X, while the protection level is IP2X between small rooms and when the circuit breaker door is open. The installation and maintenance of the cabinet can be carried out on the front or back. The switchgear can not only be installed in a face-to-face or back-to-back double row arrangement, but also can be installed against the wall according to specific project requirements, which saves floor space and improves the safety and flexibility of the switchgear.

    Outline Dimension and Schematic Diagram of Switchgear Structure

    Switchgear Structure Diagram 1Switchgear Structure Diagram 2
    1. Shell
    2. Valve bracket
    3. Circuit breaker trolley
    4. Contact box
    5. Busbar sleeve
    6. Instrument room
    7. Pressure relief device
    8. Current transformer
    9. Ground switch

    Technical Parameter

    Item Unit Argument
    Rated voltage kV 40.5
    Rated frequency Hz 50
    Rated current of main busbar A 630, 1250, 1600, 2000
    Rated current of branch busbar A 630, 1250, 1600
    Phase-phase, phase-ground Isolating distance
    Rated insulation level 1min power frequency withstand voltage (effective value) kV 95 115
    Lightning impulse withstand voltage (peak value) kV 185 215
    1min power frequency withstand voltage of auxiliary control circuit V 2000
    Rated short-circuit breaking current kA 25, 31.5
    Rated short-circuit making current (peak value) kA 63, 80
    Rated short-time withstand current (4S) kA 25, 31.5
    Rated peak withstand current kA 63, 80
    Rated voltage of auxiliary control circuit V AC or DC 110V/220V
    Protection level IP4X/IP2X
    Outline dimension (Width×Depth×Height) mm 1400x2800(3000)x2800 (*number in parentheses represents SF6 trolley solution)
    Weight kg About 2300

    Frequently Asked Questions (FAQ)

    Q: What are the standard ambient conditions for operating this switchgear?

    A: The switchgear is designed for use at altitudes ≤1000m, with ambient temperatures ranging from -15℃ to +40℃. The daily average relative humidity should not exceed 95% (monthly average ≤90%), and the seismic intensity must not exceed 8 degrees. It is not suitable for environments with corrosive or flammable gases.

    Q: Which circuit breaker models are compatible with this switch cabinet?

    A: The switch cabinet body can be equipped with the ZN85A vacuum circuit breaker, French Schneider's SF1 and SF2 types, and the Alstom FP series SF6 circuit breaker to meet diverse application requirements.

    Q: How does the switchgear ensure safety during operation?

    A: It features a complete metal armor and fully enclosed structure with four independent compartments. It incorporates a "five prevention" function design to prevent misoperation, such as pushing the trolley with a load, accidental entry into live compartments, and operating the circuit breaker under unsafe conditions.

    Q: What is the ingress protection (IP) rating of the switchgear?

    A: The protection rating of the outer shell is IP4X. The protection level between individual internal compartments and when the circuit breaker door is open is IP2X.

    Q: Can this switchgear be installed against a wall to save space?

    A: Yes. The cabinet installation and maintenance can be performed from both the front and back. It supports face-to-face, back-to-back, or against-the-wall installation layouts depending on specific project needs.