KYN28-24 High Voltage Switchgear Cabinet - IEC Certified 24kV Metal-Enclosed Power Distribution from China Suppliers & Factory
Model Meaning
Product Standard
- GB311.1 Insulation co-ordination - Part 1: Definitions, principles and rules
- GB1984 High-voltage alternating-current circuit-breakers
- GB3906 Alternating-current metal-enclosed switchgear and controlgear for rated voltages above 3.6kV and up to and including 40.5kV
- GB/T11022 Common specifications for high-voltage alternating-current switchgear and controlgear standards
- Common specifications for high-voltage switchgear and controlgear standards
- IEC62271-200:2003 High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 52kV
Conditions of Use
- Altitude: ≤1000m;
- Ambient temperature: upper limit of ambient air temperature +40℃, lower limit -15℃;
- Relative humidity: The daily average relative humidity shall not exceed 95%; monthly average relative humidity shall not exceed 90%;
- Seismic intensity: The seismic intensity does not exceed 8 degrees;
- It's not suitable for places with obvious pollution such as corrosive or flammable gas and water vapor, etc.
- When the above normal service conditions are not met, the user can negotiate with the manufacturer.
Product Characteristics
- The switchgear is designed with complete metal armor and fully enclosed structure.
- The interior of the switchgear is divided into four independent compartments: circuit breaker room, busbar room, cable room and relay instrument room. Each functional unit is sealed with metal plates and equipped with independent pressure release channel and release door.
- The switch cabinet body is made of high-quality cold-rolled steel plate processed by CNC sheet metal forming, and connected by high-strength bolts, nuts and rivet nuts. The surface of the components is sprayed or galvanized; it can be equipped with VS1(ZN63A) vacuum circuit breaker and ABB's VD4 and Schneider's HVX series circuit breakers to meet the needs of different users.
- The switchgear can perform circuit breaker opening and closing, moving-in/out, and ground switch opening and closing with the cabinet door closed.
- The switchgear is designed to prevent misoperation of circuit breaker, prevent pushing trolley with load, prevent ground switch from transmitting power at the grounding position, and prevent accidental entry into live compartments, meeting the "five prevention" functions.
- The convenient door panel observation window of the switchgear allows for viewing of the circuit breaker's on/off status, trolley position, energy storage position, and ground switch's on/off status.
- The switchgear trolley has good interchangeability, and the secondary wires are located in spacious cable tray, which are beautiful and easy to find. The primary cable connection is convenient.
- The protection level of the outer shell is IP4X, while the protection level is IP2X between small rooms and when the circuit breaker door is open. The installation and maintenance of the cabinet can be carried out on the front or back. The switchgear can not only be installed in a face-to-face or back-to-back double row arrangement, but also can be installed against the wall according to specific project requirements, which saves floor space and improves the safety and flexibility of the switchgear.
Schematic Diagram of Switchgear Structure
Technical Parameter
| Item | Unit | Argument | ||||
| Rated voltage | kV | 24 | ||||
| Rated frequency | Hz | 50/60 | ||||
| Rated insulation level | 1min power frequency withstand voltage (effective value) | kV | Phase-phase, phase-ground | 65 | Isolating distance | 79 |
| Lightning impulse withstand voltage (peak value) | kV | 125 | 145 | |||
| Power frequency withstand voltage of auxiliary control circuit | V | 2000 | ||||
| Rated current | A | 63,012,501,600,200,000,000,000 | ||||
| Rated short-circuit breaking current | KA | 20 | 25 | 31.5 | ||
| Rated short-circuit making current (peak) | KA | 50 | 63 | 80 | ||
| Rated short-time withstand current (4s) | KA | 20 | 25 | 31.5 | ||
| Rated peak withstand current | KA | 50 | 63 | 80 | ||
| Rated voltage of auxiliary control circuit | V | 110V/220V DC or AC 110V/220V | ||||
| Protection level | IP4X/IP2X | |||||
| Outline dimension (Width×Depth×Height) | mm | 800×1810×2430 / 1000×1810×2430 | ||||
| Weight | kg | 840~1440 | ||||
Frequently Asked Questions (FAQ)
Q What manufacturing and safety standards does this switchgear comply with?
This switchgear complies with several international and national standards, including GB311.1, GB1984, GB3906, GB/T11022, and IEC62271-200:2003 for high-voltage AC metal-enclosed switchgear.
Q What are the standard environmental conditions required for operating this equipment?
It is designed for altitudes ≤1000m, ambient temperatures between -15℃ and +40℃, and daily average relative humidity ≤95% (monthly average ≤90%). The location should be free from obvious pollution, corrosive or flammable gases, and water vapor.
Q Which circuit breakers are compatible with this switch cabinet?
The switch cabinet can be flexibly configured with VS1(ZN63A) vacuum circuit breakers, ABB's VD4 series, or Schneider's HVX series circuit breakers to satisfy diverse user requirements.
Q What safety features are integrated into the compartment design?
The interior features four independent compartments (circuit breaker, busbar, cable, and relay instrument rooms) sealed with metal plates. Each compartment has its own pressure release channel and door. It also features a "five prevention" interlock mechanism to prevent misoperations under load or entry into live compartments.
Q What is the ingress protection (IP) rating of the enclosure?
The outer shell provides an IP4X protection level. The protection level is IP2X between individual small compartments and when the circuit breaker door is open.