China Low Voltage Withdrawable Switchgear Suppliers for Factories and Power Distribution Solutions
Hot Products

China Low Voltage Withdrawable Switchgear Suppliers for Factories and Power Distribution Solutions

This series of low-voltage withdrawable switchgear is designed for a wide range of applications including power plants, substations, petrochemical industries, metallurgical steel rolling, transportation energy, light industry, textile manufacturing, and various mining enterprises. Ideal for residential areas and high-rise buildings, this switchgear plays a crucial role in power conversion, distribution, and control of electrical systems. It operates within a frequency range of AC 50-60Hz and is rated for working voltages of AC 660V and below, ensuring reliability in diverse environments. As a trusted supplier in China, our factory is committed to delivering high-quality switchgear solutions that meet the needs of modern energy systems

    Conditions of use

    • The ambient air temperature shall not be higher than +40℃ and not lower than -5℃, and its average temperature within 24 hours shall not be higher than +35℃;
    • Relative humidity: in clean air, it doesn’t exceed 50% at a maximum temperature of +40°C; higher relative humidity is allowable at lower temperatures (e.g. 90% at +20°C); however, it should be considered that occasional condensation may occur due to temperature change.
    • Altitude shall not exceed 2000m;
    • This equipment is suitable for transportation and storage at temperatures ranging from -25℃ to +55℃, and it can reach +70℃ in a short period of time (not exceeding 24 hours). At these extreme temperatures, the equipment should not suffer any irreparable damage and should be able to function normally under normal conditions;

    ◆ Note: When the above normal service conditions cannot meet the usage requirement, it shall be negotiated between the user and the manufacturer.

    ◆ When this equipment is used on offshore oil drilling platforms and nuclear power plants, a separate technical agreement should be signed.

    Technical parameter

    Rated insulation voltage AC690V
    Rated working voltage AC400V
    Rated current of main busbar ≤6300A
    Rated withstand current of main busbar(1s) 50kA, 80kA
    Rated peak withstand current of main busbar 105kA, 176kA
    Maximum working current of distribution busbar (vertical busbar) 1000A
    Distribution busbar(peak current of vertical busbar)  
      Standard type 105kA(maximum)/0.1s
      Enhanced type 176kA(maximum)/0.1s

    Protection level

    Compliant with IEC529 and DIN40050 standards

    • IP30 provides protection for solid larger than φ2.5MM
    • IP40 provides protection for solid larger than φ1.0MM
    • IP54 provides protection against dust and splash in any direction

    ◆ When ordering IP54 protection level, it should be negotiated with the manufacturer.

    Cabinet structure

    The basic structure of the switchgear cabinet is assembled by C-shaped profiles. C-shaped profiles are made by bending steel plates with E=25mm as the modular installation hole.

    All cabinet frames and inner partitions are treated with galvanized purification. The surrounding door panels and side panels are coated with high-voltage electrostatic spraying.

    The basic structure of the cabinet is shown in Figure 1; the basic dimensions of the cabinet are shown in Figure 2, Tables 1 and 2.

    Switch cabinet type

    Power distribution center cabinet (PC): Emax, MT, 3WN, AH, ME series circuit breakers can be used.

    Motor control center cabinet (MCC): Assembled from draw-out units of various sizes, the main switch of each circuit adopts a high breaking molded case circuit breaker or rotary load switch with fuse. Power factor automatic compensation cabinet (with manual, automatic and remote power factor compensation device).

    Cabinet frame structure composed of c-shaped profiles (Figure 1)

    Cabinet frame structure composed of c-shaped profiles

    Cabinet schematic diagram (Figure 2)

    Cabinet schematic diagram

    Installation diagram

    Solution 1: Welding installation

    Solution 2: Bolt installation

    Installation diagram

    Installation diagram of busbar bridge

    Installation diagram of busbar bridge

    Frequently Asked Questions

    What are the ambient temperature requirements for this equipment?
    The ambient air temperature must be between -5℃ and +40℃, with a 24-hour average temperature not exceeding +35℃.
    What is the maximum operating altitude for the switchgear cabinet?
    The installation and operating altitude for this equipment should not exceed 2000 meters.
    What is the difference between standard and enhanced distribution busbars?
    The Standard type has a peak current capacity of 105kA (maximum)/0.1s, while the Enhanced type offers a higher peak current capacity of 176kA (maximum)/0.1s.
    What IP protection levels can be ordered for this switchgear?
    The cabinet complies with IEC529 and DIN40050 standards. It is available in IP30 (protection against solids >2.5mm), IP40 (protection against solids >1.0mm), and IP54 (protection against dust and splashes). IP54 requires negotiation with the manufacturer.
    How is the cabinet frame structured and treated?
    The frame is assembled using C-shaped profiles with E=25mm modular installation holes. All frames and internal partitions are galvanized, while the door and side panels are coated with high-voltage electrostatic spraying.